Getting for the alarm status and the notification resource of the project session
REQ[{owner}-{grp}]: <get path="/UI/VCAEngine/ses_{session}/%2fserv%2falarm" mode="{mode}" tp="{typeNtf}" wdg="{widget}" />
  • owner, grp — reading access for the project owner or a user in group and regarding to the project permissions;
  • session — identifier of the session;
  • mode — the requesting mode, only "resource" for obtaining the notification resources and empty for the status only;
  • typeNtf — the notification type of obtaining the notification resource, see the alarming section;
  • widget — address of the widget for forming the notification resource, empty for global.
RESP: <get path="/UI/VCAEngine/ses_{session}/%2fserv%2falarm" mode="{mode}" tp="{typeNtf}" rez="0" alarmSt="{alarmSt}" tm="{clock}" wdg="{widget}" resTp="{resTp}" mess="{message}" lang="{language}">{resource}</get>
  • alarmSt — the alarm status as that described in the alarming section;
  • clock — the internal clock (the live cycle) value at the notification resource form;
  • widget — address of the source widget at the notification resource form;
  • message — message of notification from the text;
  • language — language of the notification, for the "message" mostly;
  • resTp — type of the notification resource;
  • resource — resource of the notification encoded by Base64 for the binary data.
<get path="/UI/VCAEngine/ses_AGLKS/%2fserv%2falarm" mode="resource" tp="1" rez="0" user="roman"
     alarmSt="460554" tm="0" resTp="audio/ogg;73.3428" lang="en_US.UTF-8">
T2dnUwACA...Dg6gwAjo+PAQ==