OpenSCADA server infrastructure representing, tracing and managing.
- RS-400-PSAP-I3: Effectivity drop down to 75%, high electricity noise and low -12V (very influence on RS232 and USB) => REPLACED by FSP350-60EGN
- 2024-08-14: Measured PS effectivity up to 94% and the consume power of the Server from 38W.
- AMD Phenom(tm) II X4 900e + GA-M68M-S2P + DDR2-4GB: Consume power more 60W, has only 4GB, can be improved for the performance => REPLACED by AMD Phenom II x4 910e + GA-M68MT-D3 + DDR3-8GB
- 2024-07-15: Consume power from 46W, has 8GB, improves in the performance up to 20% on high load and memory active real tasks.
- ST1000VM002: stopping sometimes, seems after accessing to some sectors => REPLACED by the brand new one SSD KODAK X120 PRO 1TB
- 2024-06-25 => Appeared 32 pending sectors
- speed of the SATA interface dropped down to 1.5 Gbps by MB itself
- 2019-04-25 06:00 => This HDD connected to SATA2 and WD to SATA1
- 2019-01-11 19:03 => Swap the SATA port between the WD HDD
- 2018-06-15 22:45 => The SATA cable was replaced on 22.06.2018
- WD10EZRX: appearing the reallocated sectors => REPLACED by the brand new one SSD IRP-SSDPR-S25C-01T
- 2021-10-05 22:03: The DATA partition was dropped out the RAID, Reallocated_Sector_Ct achieved up to 1082 and the problematic-slow disk space is 0.12(0.9...1.02)% = 1GB.
- 2021-08-10 06:39: 57 Reallocated_Sector_Ct, 9 Reallocated_Event_Count
- M2NPV-VM: several problems in stability => REPLACED by GA-M68M-S2P
- 2022-06-27: the MB started after about 30 minutes at restart for the UPS battery one year test => unsuccessfully tried for start after the MB discharging procedure and discharging the MB capacitors
- 2022-02-02: the MB started after about several minutes of cooling at some service restart
- LPM-MG12-65Ah: brand new one 2021.02 that is dead again after two years and about 102 partial and 57 whole cycles on 12.5Ah (from 65Ah) => DEAD
- Logic Power batteries are DUNG!
- 2023-06-20: Capacity = 12.5 Ah (5 hours at 2.5A)
- 2022-06-29: R = 12 mOm, Capacity = 70.5 Ah (28.2 hours at 2.5A)
- 2021-06-18: R = 16 mOm, Capacity = 75 Ah (30 hours at 2.5A)
- LPM-MG12-65Ah: brand new one 2018 that is dead mostly after two years on 27Ah (from 65Ah) => REPLACED
- 2021-06-01: Capacity = 27 Ah (10.7 hours at 2.5A), by the USB-Meter: 30(-6%)Ah
- 2020-09-15: Capacity = 46 Ah (18.2 hours at 2.5A), by the USB-Meter: 49(-6%)Ah
- 2019-06-15: R = 46 mOm, Capacity = 68 Ah (27.5 hours at 2.5A), by the USB-Meter: 71(-6%)Ah
- 6CT-60-A3 (12V 60Ah, 170x240x190, 2016-05): an automobile starter accumulator, so it was dead on 6Ah (from 65Ah) after three years => REPLACED
- 2019-06-13: R = 90 mOm, Capacity = 5.7Ah, 5.9(-6%)Ah
- 2018-09-11: ~2.5 hours at (86+33)W = 25Ah
- 2018-08-18: 52Ah
- 13.5V -> 8.2V = 52Ah;
- 8.2V -> 14.3V = 46Ah (30°C -> 33.5°С)
- 13.6V - 6h -> 13.3V
- 2016-05: 4 hours at (84+33)W = 39Ah
- 16.7 hours at 33W(2.5A) = 42Ah
- Temperature sensor DS18B20 (288C704A0000001F): freezes in the measuring => NOT OBSERVED
- 2019-02: failure in the measuring freeze => restored after the power reset
|