From OpenSCADAWiki
Jump to: navigation, search

With this tab you can set:

  • State of the controller object, that is: status, "Enabled", "Running" and the storage name containing the configuration.
At.png Manual restart of the enabled controller object causes the force resync at the sync period >= 0.
  • Identifier, name and description of the controller.
  • The state "Enabled" and "Running" in which the controller object must be translated at start up.
  • Acquisition schedule policy and priority of the data acquisition task.
  • Time interval of repetition attempts to restore communication with the lost station, in seconds.
  • Maximum depth of data of the archive values and messages to restore when start, in the hours. Zero for disable the remote archive access.
  • Asynchronous writing. Enables of writing in the common acquisition cycle for the buffer of accumulated values, by one request.
At.png Useful for slow and not reliable networks-connections since the writing buffer stores data before the connection restore and the real writing.
  • Level of requested messages of the data sources. Also enables the DAQ-messages of the User API function messSet() transferring to the lower stations.
  • Synchronization time with the remote station in seconds. Zero to disable the periodic sync and -1 for the sync disabling at the start also.
  • Remote OpenSCADA station of the reflected data. Several stations in the list enable the vertical redundancy mechanism.
  • List of the reflected controller objects and parameters. The list can be used as for controller objects for the reflection of all their parameters, and for individual parameters too.
  • Command to go to configuration of the OpenSCADA remote stations list.
  • Allow the automatic removal of parameters and attributes to update to the actual state.
At.png In the production mode, it's better to turn this off!
  • Placing different controllers to the different virtual parameters.