From OpenSCADAWiki
Template IOs
Identifier | Parameter | Type | Mode | Attribute | Configuration | Value |
---|---|---|---|---|---|---|
answer | Answer to the password request | String | Input | Read only | Variable | |
TS | Read energy of tariffs sum | Boolean | Input | Not attribute | Constant | 0 |
T1 | Read energy of tariff 1 | Boolean | Input | Not attribute | Constant | 0 |
T2 | Read energy of tariff 2 | Boolean | Input | Not attribute | Constant | 0 |
T3 | Read energy of tariff 3 | Boolean | Input | Not attribute | Constant | 0 |
T4 | Read energy of tariff 4 | Boolean | Input | Not attribute | Constant | 0 |
P | Read power P | Boolean | Input | Not attribute | Constant | 0 |
Q | Read power Q | Boolean | Input | Not attribute | Constant | 0 |
S | Read power S | Boolean | Input | Not attribute | Constant | 0 |
U | Read voltage U | Boolean | Input | Not attribute | Constant | 0 |
I | Read current I | Boolean | Input | Not attribute | Constant | 0 |
K | Read power coefficient | Boolean | Input | Not attribute | Constant | 0 |
F | Read frequency F | Boolean | Input | Not attribute | Constant | 0 |
N | Read serial number | Boolean | Input | Not attribute | Constant | 0 |
TSAp | Energy from resetting, tariffs sum A+ | Real | Input | Read only | Variable | |
TSAm | Energy from resetting, tariffs sum A- | Real | Input | Read only | Variable | |
TSRp | Energy from resetting, tariffs sum R+ | Real | Input | Read only | Variable | |
TSRm | Energy from resetting, tariffs sum R- | Real | Input | Read only | Variable | |
T1Ap | Energy from resetting, tariff 1 A+ | Real | Input | Read only | Variable | |
T1Am | Energy from resetting, tariff 1 A- | Real | Input | Read only | Variable | |
T1Rp | Energy from resetting, tariff 1 R+ | Real | Input | Read only | Variable | |
T1Rm | Energy from resetting, tariff 1 R- | Real | Input | Read only | Variable | |
T2Ap | Energy from resetting, tariff 2 A+ | Real | Input | Read only | Variable | |
T2Am | Energy from resetting, tariff 2 A- | Real | Input | Read only | Variable | |
T2Rp | Energy from resetting, tariff 2 R+ | Real | Input | Read only | Variable | |
T2Rm | Energy from resetting, tariff 2 R- | Real | Input | Read only | Variable | |
T3Ap | Energy from resetting, tariff 3 A+ | Real | Input | Read only | Variable | |
T3Am | Energy from resetting, tariff 3 A- | Real | Input | Read only | Variable | |
T3Rp | Energy from resetting, tariff 3 R+ | Real | Input | Read only | Variable | |
T3Rm | Energy from resetting, tariff 3 R- | Real | Input | Read only | Variable | |
T4Ap | Energy from resetting, tariff 4 A+ | Real | Input | Read only | Variable | |
T4Am | Energy from resetting, tariff 4 A- | Real | Input | Read only | Variable | |
T4Rp | Energy from resetting, tariff 4 R+ | Real | Input | Read only | Variable | |
T4Rm | Energy from resetting, tariff 4 R- | Real | Input | Read only | Variable | |
PS | Power P(W) by the phases sum | Real | Input | Read only | Variable | |
P1 | Power P(W) by the phase 1 | Real | Input | Read only | Variable | |
P2 | Power P(W) by the phase 2 | Real | Input | Read only | Variable | |
P3 | Power P(W) by the phase 3 | Real | Input | Read only | Variable | |
QS | Power Q(var) by the phases sum | Real | Input | Read only | Variable | |
Q1 | Power Q(var) by the phase 1 | Real | Input | Read only | Variable | |
Q2 | Power Q(var) by the phase 2 | Real | Input | Read only | Variable | |
Q3 | Power Q(var) by the phase 3 | Real | Input | Read only | Variable | |
SS | Power S(VA) by the phases sum | Real | Input | Read only | Variable | |
S1 | Power S(VA) by the phase 1 | Real | Input | Read only | Variable | |
S2 | Power S(VA) by the phase 2 | Real | Input | Read only | Variable | |
S3 | Power S(VA) by the phase 3 | Real | Input | Read only | Variable | |
U1 | Voltage U(V) by the phase 1 | Real | Input | Read only | Variable | |
U2 | Voltage U(V) by the phase 2 | Real | Input | Read only | Variable | |
U3 | Voltage U(V) by the phase 3 | Real | Input | Read only | Variable | |
I1 | Current I(A) by the phase 1 | Real | Input | Read only | Variable | |
I2 | Current I(A) by the phase 2 | Real | Input | Read only | Variable | |
I3 | Current I(A) by the phase 3 | Real | Input | Read only | Variable | |
KS | Power coefficient by the phases sum | Real | Input | Read only | Variable | |
K1 | Power coefficient by the phase 1 | Real | Input | Read only | Variable | |
K2 | Power coefficient by the phase 2 | Real | Input | Read only | Variable | |
K3 | Power coefficient by the phase 3 | Real | Input | Read only | Variable | |
F1 | Frequency F(Hz) | Real | Input | Read only | Variable | |
N1 | Serial number | String | Input | Read only | Variable | |
netaddr | Network address (0...240) | Integer | Input | Not attribute | Constant | 1 |
password | Password | String | Input | Not attribute | Constant | 111111 |
transport | Transport | String | Input | Not attribute | Constant | merc230 |
f_stop | Function stop flag | Boolean | Input | Not attribute | Variable | 0 |
f_err | Function error | String | Input | Not attribute | Variable | 0 |
f_start | Function start flag | Boolean | Input | Not attribute | Variable | 0 |
f_frq | Function calculate frequency (Hz) | Real | Input | Not attribute | Variable | 1000 |