From OpenSCADAWiki
Jump to: navigation, search

Template IOs

Identifier Name Type Mode Attribute Configuration Value
in Input Real Input Not attribute Link Input|var
inProc Input processing procedure Text Input Not attribute Constant
var Variable Real Input Read only Variable 0
ed Dimension String Input Full access Variable
min Scale: minimum Real Input Full access Variable 0
max Scale: maximum Real Input Full access Variable 100
scSqr Scale: square Boolean Input Full access Variable 0
subMode Substitute: mode Integer numbers selection Input Full access Variable 0

0;1;2
no;last;substitute

subVar Substitute: variable Real Input Full access Variable 0
alSup Violations suppress Boolean Input Full access Variable
alDelay Violations delay, seconds Real Input Full access Variable 0
aMin Border down alarm Real Input Full access Variable 0
aMax Border up alarm Real Input Full access Variable 0
wMin Border down warning Real Input Full access Variable 0
wMax Border up warning Real Input Full access Variable 0
HystBnd Hysteresis of borders violation Real Input Full access Variable 1
speed Motion speed, %/cycle Real Input Full access Variable 0
prec Precision, signs Integer Input Full access Variable 2
log Logarithmic scale Boolean Input Full access Variable 0
Tf Filter time, seconds Real Input Full access Variable 0
iAdd Input addition Real Input Not attribute Constant 0
iMult Input multiplication Real Input Not attribute Constant 1
plcMin Minimum module scale Real Input Not attribute Constant 0
plcMax Maximum module scale Real Input Not attribute Constant 0
plcExcess Allowed scale exceeding, % Real Input Not attribute Constant 0
plcImit PLC imitation Boolean Input Not attribute Constant 0
plcImitIn PLC imitation input Real Input Not attribute Link Imitation|var
this Object Object Output Not attribute Variable
SHIFR Code String Input Not attribute Variable
NAME Name String (translate) Input Not attribute Variable
DESCR Description Text (translate) Input Not attribute Variable
f_err Function error String Input Not attribute Variable 0
f_frq Frequency of calculation of the function, Hz Real Input Not attribute Variable 1000
f_start Function start flag Boolean Input Not attribute Variable 0
f_stop Function stop flag Boolean Input Not attribute Variable 0