To display a list of current violations, on the mnemonic scheme we will place an element of the protocol from the library of primitives "Widget"->"Library: originals"->"Protocol" and name it Protocol. In the attributes inspector we will establish the properties of the protocol:

  • "Geometry: width" — 500;
  • "Geometry: height" — 250;
  • "View columns" — "tm;lev;mess";
  • "Level" — -1, display current violations of any level;
  • "Size, seconds" — 0, display violations at any depth;
  • "Tracing period, seconds" — 1.