For any displayed or controlled parameter the passport can be obtained in runtime mode by clicking the right mouse button on the contour field. The passport will present to all the properties of the parameter.

Linking attributes

ID Parameter Data type Config Config template Description
prmId Parameter:identifier String Input link Parameter|SHIFR Parameter's identifier is used to place the record the operator's actions to the report.
prmShifr Parameter:code String Input link Parameter|NAME Short name of the parameter, code. It is placed below the frame.
prmDescr Parameter:description String Input link Parameter|DESCR Description of the parameter is used to place the record the operator's actions to the report.
prmColor Parameter:border color String Input link Parameter|color Sets the border color of the contour.
Parameters of Analog Device
prmDemention Parameter:dimension variable String Input link Parameter|ed
prmPrec Precision Integer Input link Parameter|prec Number of decimal places in parameter, step change for the manual input of values, as well as set point and out of the PID regulator.
prmVar Parameter:variable Real Full link Parameter|var Directly to the analog value of the parameter.
max Parameter:maximum Real Input link Parameter|max Upper limit value of the parameter.
min Parameter:minimum Real Input link Parameter|min Minimum limit values of the parameter.
prmAMax Upper alarm border Real Input link Parameter|aMax
prmAMin Lower alarm border Real Input link Parameter|aMin
prmWMax Upper warning border Real Input link Parameter|wMax
prmWMin Lower warning border Real Input link Parameter|wMin
Manual Analog Input
prmVarIn Parameter:variable input Real Full link Parameter|varIn Output for manual input of an analog value of the parameter. The presence of this parameter is an indication that the parameter - is determined as "Manual analog input.
PID regulator
prmAnalog Parameter:analog regulator Boolean Input link Parameter|analog Sign of the analog regulator, in case of the absence of this parameter the regulator is an analog one.
prmAuto Parameter:automate Boolean Full link Parameter|auto Mode of the regulator, "Automatic".
prmCasc Parameter:Cascade Boolean Full link Parameter|casc Mode of the regulator, "Cascade".
prmSp Parameter:set point Real Full link Parameter|sp PID regulator's set point, it can be set by the user.
prmImpQdwnTm Parameter:imp. out down Boolean Input link Parameter|impQdwn Output "Down" for impulse regulator.
prmImpQupTm Parameter:imp. out up Boolean Input link Parameter|impQup Output "Up" for impulse regulator.
prmOut Parameter:output Real Full link Parameter|out Analog PID regulator output for display and manual input of the output value of PID in manual mode.
prmManIn Parameter:manual input Real Full link Parameter|manIn Manual input of the new output value of PID regulator in manual mode.
Parameters of discrete devices
prmCom Parameter: Command - "Open" Boolean Full link Parameter|com
prmClose Parameter: Command - "Close" Boolean Full link Parameter|close
prmStop Parameter: Command - "Stop" Boolean Full link Parameter|stop
prmOpenSt Parameter: State - "Opened" Boolean Input link Parameter|st_open
prmCloseSt Parameter: State - "Closed" Boolean Input link Parameter|st_close
digComs Parameter:digital commands String Input link Parameter|digComs Names and colors of buttons of commands in the format: {On}[-color]:{Off}[-color][:{Stop}[-color]]. Default colors are: green, red and yellow.
digStts Parameter:digital states String Input link Parameter|digStts Names and colors of labels of states in the format: {On}[-color]:{Off}[-color]. Default colors are: green and red.