 h English (en){{CntHdr|Configuring and using}}
:1. Create an output transport of the type "[[Special:MyLanguage/Modules/Serial|Serial]]" and set its Identifier like to "SCU750", one for each the devices' used serial bus.
:2. Set proper address and timeouts of the [[Special:MyLanguage/Modules/Serial|Serial]] device.
:3. Create and start [[Special:MyLanguage/Modules/LogicLev|a logical controller object]] or use any present one with need scheduling properties.
:4. Create [[Special:MyLanguage/Modules/LogicLev|a logical parameter object]] and select the template for that, one for each the devices — enable the parameter.
:5. Into the tab "Template configuration" of the logical parameter object you need to set:
:* ''Transport'' — to Identifier of the transport into step 1.
:* ''Device address'' — to logical address of the device on the bus under the transport in step 1.
:* ''Period data getting'' — to needed acquisition period which more to the real processing by the logical level controller. Commands and some other functions will process immediately.
:6. RESULT: The logical parameter object will perform interaction and placing of gathered data to the parameter attributes. Also you are able to send some commands to the device through the writable attributes.