From OpenSCADAWiki
Enter a message name below to show all available translations.
Found one translation.
Name | Current message text |
---|---|
h English (en) | {{CntHdr|Configuring and using}} [[File:LibsDevsSLOTCfg.png|right|Configuration.]] :1. Create and start [[Special:MyLanguage/Modules/LogicLev|a logical controller object]] or use any present one with need scheduling properties. :2. Create [[Special:MyLanguage/Modules/LogicLev|a logical parameter object]] and select this template for it, one for each the devices — enable the parameter. :3. Into the tab "Template configuration" of the logical parameter object you need to set: :* ''Transport'' — to the address of the automatically created transport with its parameters after ":", according to [[Special:MyLanguage/Documents/User_API#SYSTransport|the function SYS.Transport.outAt() address format]]. :* ''Modem'' — here you can set the modem configuration in the format "{TelN}[:{Init1}[:{Init2}[...{InitN}]]]" if your device accessed through a modem. :* ''Modem times'' — here you can change the default modem timeouts in the form "{tm}:{ConTm}" if your device accessed through a modem. :* ''Device address [0...65535]'' — set here the device address — Serial Number converted from hex to decimal. :* ''Pipe number [0...1]'' — change here the default pipe of the device. :* ''Scheduling at CRON'' — set here the logical execution at the [[Special:MyLanguage/Documents/User_API#CRON|CRON]]. :* ''Time limit of processing the archiving, seconds'' — change here the default safety timeout. :* ''OpenSCADA archiver for device archive of days'' — set here the archive used for storing the daily (86400 seconds) values — enables the day archive reading. :* ''OpenSCADA archiver for device's archive of hours'' — set here the archive used for storing the hourly (3600 seconds) values — enables the hour archive reading. :4. RESULT: The logical parameter object will perform interaction and placing of gathered data to the parameter attributes. |