EnglishУкраїнськаmRussian
Login/New
Unanswered topic

[TaskDone] IEC 60870-5 acquisition protocol implementation


Author Message
Written on: 23. 10. 2012 [16:17]
roman
Roman Savochenko
Moderator
Contributor
Developer
registered since: 12.12.2007
Posts: 3750
Base: actuality and some requests
Funding: Successful finished. The task result fund is 100% to the real work time (laboriousness).
Priority: high
State: Done
Investors: Ustijancev Michael: 100% to the real work time (laboriousness) and the hardware access
Project page: http://oscada.org/wiki/Special:MyLanguage/Libs/Devices#IEC60870

IEC 60870 part 5 is one of the IEC 60870 set of standards which define systems used for telecontrol (supervisory control and data acquisition) in electrical engineering and power system automation applications. Part 5 provides a communication profile for sending basic telecontrol messages between two systems, which uses permanent directly connected data circuits between the systems.

Implementation status, part 104:
(+) Client-Master: Data exchanging conception.
(+) Client-Master: Data model integration and reflection to the OpenSCADA objects: the template to DAQ.LogicLev, all data (DI, DO, AO) acquisition-gather to object's attribute "items"; manual set attributes for direct representing by "itemsSet"; writing-commands support by object "items" and direct attributes.
(+) Client-Master: Function: STARTDT, STOPDT, TESTFR, Ack, C_IC_NA_1, C_CI_NA_1, C_SC_NA_1, M_SP_NA_1, M_ME_NB_1, C_CS_NA_1
(+) Client-Master: Debug and practical adaptions
(+) Preparing and placing to the OpenSCADA devices library, on the user protocol's conception. Documenting.

Learn, learn and learn better than work, work and work.



8749